Screenshot Of List Of Errors And Warnings - Kohler SFGLD480 Operation & Maintenance Manual

Generator set models 750/1000rezk
Table of Contents

Advertisement

Clicking the
button, you can access the actions menu where you can perform the following functions:
-
Confirm Alarms
-
Confirm Runtime Errors
-
Activate and deactivate automatic scrolling
A list of errors and warnings are outlined below.
ERROR CODE
Trigger number
Trigger missing
Cycle signal missing
Trigger period
Reset number
Pre-processor pickup
Overspeed
Output board missing
Output or HV error
Misfire rate
Low-power
General
Temperature
Reset by watchdog
PRODUCT INFORMATION
IO-G-M-33-010e
INSTALLATION AND OPERATION MANUAL - GIS IGNITION UNIT
Fig. 12 – Screenshot of list of errors and warnings
DESCRIPTION
Number of teeth does not coincide with the set number
Number of teeth counted is smaller than expected number
Cam signal was not detected in time. More events were
counted than expected per cycle.
Event period between two teeth was outside the expected
range.
Number of reset signals per cycle is outside expected range
Pre-processor pickup is causing an error
Overspeed
Output board could not be detected
Error occurred in output board Possible problems with
primary high voltage generator (185 V)
Misfire rate exceeded
Voltage too low
General warning
The maximum permissible device temperature was exceeded
The device was restarted by the watchdog