The exhaust pipeline shall be secured by means of collars through which it can slide and properly
distributed fixed anchorage points.
-
The exhaust pipeline and silencer shall be protected and heat-insulated to avoid big heat radiations into the
engine room and the subsequent reduction in the engine performance.
-
The exhaust pipeline must be laid for each engine individually. Never put together the gas outlets of various
engines in a single collector.
-
For completion of the exhaust pipeline, there must be a condensate trap installed at the lower end of the
last vertical run of exhaust pipe as well as one draining valve (see Figure 1).
SLIDING FIXING
FLEXIBLE
 A
Inner Diameter
 B
Exhaust Flexible Diameter
C
20 mm (0.78 inch)
PRODUCT INFORMATION
IT-G-A-00-008e
EMISSIONS - RELATED INSTALLATION INSTRUCTIONS
ALTERNATIVES TO PREVENT
WATER INFILTRATIONS
POINT
Fig. 1 – "V" Engine Installation of Exhaust Pipeline
INDEX
A
SILENCER
FLEXIBLE
DIAMETER AS PER TABLE 1
FLEXIBLE
CONDENSATE
TRAP
DRAINING VALVE
D
10 mm (0.39 inch)
E
30º (86ºF)
 A
n
4.1.54
DATE
Dep. 2
February 2010
O&M_2.002211.810_A_10_2016
2/5