4. POWER REGULATION

4.1. OBLIGATORY

Depending on ambient temperature, the power correction described in IC-G-B-00-001e should be made.
4.2. RECOMMENDED
It is advisable to regulate the engine power according to reachable values (below the shutdown-triggering
values) to avoid sudden shutdowns of the engine at facilities short of cooling.
The recommended regulations to be made with the signals of the minimum safety measures installed are shown
below.
Table 3. Configuration of power regulations
Measure
Water temperature
Engines 90/80, 90/55 and 90/40
(194/176ºF 194/131ºF y
194/104ºF)
Water temperature
Engines 120/80.120/55 and
120/40
(248/176ºF 248/131ºF y
248/104ºF)
Mixture Temperature
Engines 120/40 and 90/40
(248/104ºF y 194/104ºF).
Mixture Temperature
Engines 120/55 and 90/55
(248/131ºF y 194/131ºF)
Mixture temperature
Engine 120/80 and 90/80
(248/176ºF y 194/176ºF)
PRODUCT INFORMATION
IO-G-M-60-002e
Location
Signal type
Main Circuit
4-20 mA (0-150ºC)
Outlet
(32-302ºF)
Intake
4-20 mA (0-150ºC)
manifold
(32-302ºF)
INDEX
K
FG/FGLD/SFGLD/SFGM/SFGRD
ENGINES INSTRUMENTATION
Protection value
Linear power regulation.
 92ºC(197,6ºF):100% load
> 92ºC (197,6ºF)
 95ºC(203ºF): :20% load
Linear power regulation
 121ºC (249,8ºF): 100% load
> 121ºC (249,8ºF)
 124ºC (255,2ºF): 20% load
Linear power regulation.
 51ºC (123,8ºF): 100% load
> 51ºC (123,8ºF)
 64ºC (147,2ºF): 40% load
Linear power regulation.
 62ºC (143,6ºF): 100% load
> 62ºC (143,6ºF)
 64ºC (147,2ºF): 20% load
Linear power regulation
 84ºC (183,2ºF): 100% load
> 84ºC (183,2ºF)
 86ºC (186,8ºF): 20% load
2.9.5
DATE
Dep. 3
May 2016
O&M_2.002211.810_A_10_2016
Action
Active
Always
Always
Always
Always
Always
5/5