B.5 Drive Operations by BACnet
B.5 Drive Operations by BACnet
The drive operations that can be performed by BACnet communication depend on drive parameter settings. This section
explains the functions that can be used and related parameter settings.
u

Observing the Drive Operation

A controller can perform the following actions with BACnet communications at any time regardless of parameter settings
(except for H5-ooparameters):
• Observe drive status and drive control terminal status from a controller
• Read and write parameters
• Set and reset faults
• Set multi-function inputs.
Note:
Input settings from the input terminals So and from BACnet communications are both linked by a logical OR operation.
u

Controlling the Drive

Select an external reference and adjust the parameters in
reference using BACnet communications.
Reference Source
External Reference 1
External Reference 2
Refer to b1-01: Frequency Reference Selection for AUTO Mode on page 24
for AUTO Mode on page 25
254
Table B.1 Setting Parameters for Drive Control from BACnet
Parameter
b1-01
Frequency Reference Selection 1
b1-02
Run Command Selection 1
b1-15
Frequency Reference Selection 2
b1-16
Run Command Selection 2
for details on external reference parameter selections.
Table B.1
accordingly to start and stop the drive or set the frequency
Name
and
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
Required Setting
Refer to b1-02: Run Command Selection
2
2
2
2