C.3 Connecting to a Network
u

Recommended Cable

Secification
Cable configuration
Gauge
Wire lay
Shields
NEC type
Temperature
Note:
Cable lengths cannot exceed 152 m (500 feet) at 4800 baud.
272
Table C.2 APOGEE FLN Cable Specifications
Twisted shielded pair
2
Stranded wire: 0.2 to 1.0 mm
(24 to 16 AWG)
2
Sold wire: 0.2 to 1.5 mm
(24 to 16 AWG)
Minimum 6 twists per foot
100% foil with drain wire
UL type CMP
-10 °C to +40 °C IP20/NEMA 1, UL Type 1 Enclosure, External Heatsink
-10 °C to +50 °C IP00/Open Type Enclosure