No.
o2-04
E2-11
b3-04
V/f Gain during Speed Search
b3-06
Output Current 1 during Speed Search
b8-04
Energy Saving Coefficient Value
C6-02
Carrier Frequency Selection
E2-01
Motor Rated Current
E2-02
Motor Rated Slip
E2-03
Motor No-Load Current
E2-05
Motor Line-to-Line Resistance
E2-10
Motor Iron Loss for Torque Compensation
L2-02
Momentary Power Loss Ride-Thru Time
L2-03
Momentary Power Loss Minimum Baseblock Time
L2-04
Momentary Power Loss Voltage Recovery Time
L3-24
Motor Acceleration Time for Inertia Calculations
L8-02
Overheat Alarm Level
L8-35
Installation Method Selection
L8-38
Carrier Frequency Reduction Selection
n1-03
Hunting Prevention Time Constant
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
Name
Model
Drive Model Selection
Motor Rated Power
Unit
5A0125
Hex.
D5
90
kW (HP)
(125)
%
80
0.5
61.50
7
A
125
Hz
1.39
A
37.5
Ω
0.079
W
2150
s
2.0
s
2.0
s
1.7
s
0.592
°C
110
0
2
ms
30
A.18 Defaults by Drive Model
Default Settings
5A0145
5A0192
D6
D7
110
160
(150)
(200)
80
80
0.5
0.5
58.67
49.90
7
7
145
192
1.40
1.35
43.2
57.6
0.060
0.037
2150
2850
2.0
2.0
2.0
2.0
1.8
2.0
0.646
0.673
110
110
0
0
2
2
30
30
5A0242
D9
185
(250)
80
0.5
42.90
7
242
1.35
57.6
0.037
2850
2.0
2.0
2.0
0.864
110
0
2
30
A