YASKAWA Z1000 CIMR-ZU*A Series Programming Manual page 139

For hvac fan and pump
Hide thumbs Also See for Z1000 CIMR-ZU*A Series:
Table of Contents

Advertisement

n
S2-03/S2-08/S2-13/S2-18: Sequence Timers 1 to 4 Day Selection
Sets the days for which sequence timers 1 to 4 are active.
No.
S2-03
S2-08
S2-13
S2-18
Setting 0: Timer Disabled
Setting 1: Daily
Setting 2: Mon - Fri
Setting 3: Sat - Sun
Setting 4: Monday
Setting 5: Tuesday
Setting 6: Wednesday
Setting 7: Thursday
Setting 8: Friday
Setting 9: Saturday
Setting 10: Sunday
n
S2-04/S2-09/S2-14/S2-19: Sequence Timers 1/2/3/4 Selection
Sets the action that occurs when sequence timers 1 to 4 are active.
Note:
1. Setting 3 is available in drive software versions PRG: 8552 and later.
2. Setting 3 is not available in drive models 4A0930 and 4A1200.
No.
S2-04
S2-09
S2-14
S2-19
Setting 0: Digital Output Only
Setting 1: Run
Setting 2: Run - PI Disable
Setting 3: Allow Alternation
When Sequence Selection is set to Allow Alternation and that timer is enabled (S2-03, S2-08, S2-13, S2-18 > 0), the drive
will only allow MEMOBUS alternation to occur during the time specified in the corresponding Sequence Timer. Alternation
is disabled when the timer deactivates.
n
S2-05/S2-10/S2-15/S2-20: Sequence Timers 1/2/3/4 Reference Source
Selects the frequency reference source used for running the drive when sequence timers 1 to 4 are active (only applicable when
S2-04/S2-09/S2-14/S2-19 are set to 1 or 2).
Note:
H1-oo = 12/13 overrides these sequence timer run sources in drive software versions PRG: 1018 and later.
No.
S2-05
S2-10
S2-15
S2-20
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
Name
Sequence Timer 1 Day Selection
Sequence Timer 2 Day Selection
Sequence Timer 3 Day Selection
Sequence Timer 4 Day Selection
Name
Sequence Timer 1 Selection
Sequence Timer 2 Selection
Sequence Timer 3 Selection
Sequence Timer 4 Selection
Name
Sequence Timer 1 Reference Source
Sequence Timer 2 Reference Source
Sequence Timer 3 Reference Source
Sequence Timer 4 Reference Source
1.11 S: Special Parameters
Setting Range
0 to 10
0 to 10
0 to 10
0 to 10
Setting Range
0 to 3
0 to 3
0 to 3
0 to 3
Setting Range
0 to 6
0 to 6
0 to 6
0 to 6
Default
0
0
0
0
Default
0
0
0
0
1
Default
0
0
0
0
139