YASKAWA Z1000 CIMR-ZU*A Series Programming Manual page 145

For hvac fan and pump
Hide thumbs Also See for Z1000 CIMR-ZU*A Series:
Table of Contents

Advertisement

Fwd Run
Bypass Run
Drive Enable-Customer
Safeties
Override (Smoke Purge)
Drive/Bypass Select
BAS Interlock
BP Drive Relay Contact
Output
BP Bypass Relay Contact
Output
BP BAS Interlock Contact
Output
Output Frequency
Emergency Override
When the Emergency Override (Smoke Purge) digital input is closed, the drive will perform the transfer.
Transfer to Bypass on page 144
If programmed, the BP BAS Interlock Relay Contact will close before the transfer occurs. During the transfer process, and if
BAS Interlocks are present, the BAS Interlock Input MFDI must be closed before the drive will close the bypass contactor to
run the motor on line voltage.
When the Emergency Override MFDI is closed, the state of BP Drive/Bypass Select MFDI, Run command, Bypass Run
command and BP Customer Safeties MFDI have no impact on the operation of the system. When Emergency Override opens,
the drive operates based on the other digital input commands. If the drive is commanded to run, the drive will perform the
switch.
Refer to Transfer to Drive Operation on page 144
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
Speed
Search
Occurs
L2-03
Figure 1.77 Transfer to Bypass and Safety Circuit
for details.
for details.
1.11 S: Special Parameters
Refer to Immediate
1
145