1.11 S: Special Parameters
AUTO Mode Selection
(H1-oo = 6D)
Open
Closed
-
-
If S5-04 is set to 0, the AUTO and HAND multi-function inputs (setting 6D and 6E) can only be used individually or an oPE03
error will occur.
Setting 2: Normal Operation Mode with Memory
When switching AUTO/HAND modes from the HOA keypad, the drive will memorize the operation mode when the power
to the drive is shut off. This will be the initial operating mode when power is reapplied.
When switching AUTO/HAND modes from a Multi-Function Input, the drive will start with the Multi-Function Input setting.
HAND mode: The drive starts with the OFF mode when cycling the power to the drive.
AUTO mode: The drive starts with the AUTO mode when cycling the power to the drive.
OFF mode: The drive starts with the OFF mode when cycling the power to the drive.
n
S5-05: HAND Frequency Reference 1
Sets the frequency reference used in HAND mode when S5-01 is set to 3.
Note:
Setting units and range are determined by parameters o1-03, o1-10, and o1-11.
No.
S5-05
n
S5-07: HAND Key Function Selection (HOA Keypad)
Determines whether the HAND key on the HOA keypad will be enabled for switching between HAND and AUTO.
No.
S5-07
Setting 0: Disabled
Setting 1: Enabled
152
Table 1.32 HAND/AUTO Multi-Function Inputs, Legacy Behavior (S5-04 = 0)
HAND Mode Selection
(H1-oo = 6E)
-
-
Open
Closed
S5-02 = 1 AND
S5-02 = 1 AND
HAND key
AUTO key
Figure 1.83 Legacy Behavior (S5-04 = 0)
Name
HAND Frequency Reference 1
Name
HAND Key Function Selection (HOA Keypad)
Frequency Reference
Based on S5-01
Based on b1-01
Based on b1-01
Based on S5-01
OFF key AND o2-02 = 1
AUTO
Fref
via b1-01
Run
via b1-02
AUTO key
OR run command
HAND key
HAND
Fref
via S5-01
Run
On
OFF key
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
Run Command
Based on b1-02
OFF
Fref
via b1-01
Run
Off
Setting Range
0.00 to [E1-04]
Setting Range
0, 1
Default
0.00 Hz
Default
1