Metasys N2 Binary Output (Bo) Summary - YASKAWA Z1000 CIMR-ZU*A Series Programming Manual

For hvac fan and pump
Hide thumbs Also See for Z1000 CIMR-ZU*A Series:
Table of Contents

Advertisement

D.7 Metasys N2 Point Database
Object ID
Object Name
BI 10
Multi-Function Output 1 (H2-01)
BI 11
Multi-Function Output 2 (H2-02)
BI 12
Multi-Function Output 3 (H2-03)
BI 13
Safety Interlock Monitor
BI 14
HAND/AUTO Reference Monitor
BI 15
Multi-Function Input S3 Monitor
BI 16
Multi-Function Input S4 Monitor
BI 17
Multi-Function Input S5 Monitor
BI 18
Multi-Function Input S6 Monitor
BI 19
Multi-Function Input S7 Monitor
u

Metasys N2 Binary Output (BO) Summary

Object ID
Object Name
BO 1
Run Forward Command
BO 2
Run Reverse Command
BO 3
Serial Fault (EF0) Command
BO 4
Fault Reset Command
BO 5
Multi-Function Input S3 (H1-03)
BO 6
Multi-Function Input S4 (H1-04)
BO 7
Multi-Function Input S5 (H1-05)
BO 8
Multi-Function Input S6 (H1-06)
BO 9
Multi-Function Input S7 (H1-07)
BO10
Panel Lock
BO 11
Communication Fault Enable
298
Default
0
Off
0
Off
0
Off
0
Safety Clear Terminal 3 Closed
0
REMOTE
0
Off
0
Off
0
Off
0
Off
0
Off
Table D.7 Metasys N2 Binary Output Summary (Z1000 to Metasys N2)
Default
0
Stop
0
Stop
0
No Fault
0
No Reset
0
Off
0
Off
0
Off
0
Off
0
Off
LOCAL/REMOTE and Stop/Reset Keys
0
Enabled
0
EF0 Not Activated if Cable Loss Occurs
Off (0) State
Off (0) State
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
On (1) State
On
On
On
Safety Set Terminal 3 Open
LOCAL
On
On
On
On
On
On (1) State
Forward
Reverse
Fault
Reset
On
On
On
On
On
LOCAL/REMOTE and Stop/Reset Keys
Disabled
EF0 Activated if Cable Loss Occurs

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cimr-zu series

Table of Contents