YASKAWA Z1000 CIMR-ZU*A Series Programming Manual page 63

For hvac fan and pump
Hide thumbs Also See for Z1000 CIMR-ZU*A Series:
Table of Contents

Advertisement

Setting
Specification
8
50 Hz, Mid starting torque
9
50 Hz, High starting torque
A
60 Hz, Mid starting torque
B
60 Hz, High starting torque
C
90 Hz (with 60 Hz base)
D
120 Hz (with 60 Hz base)
E
180 Hz (with 60 Hz base)
F
60 Hz
<1>
<1> Setting F enables a custom V/f pattern by changing parameters E1-04 to E1-13. When the drive is shipped, the default values for parameters E1-04
to E1-13 are equal to predefined V/f pattern 7.
The following tables show details on predefined V/f patterns.
Predefined V/f Patterns for Models 5A0003 to 5A0009
Setting = 0
50 Hz
575
43.1
25.9
0
1.3 2.5
50
Frequency (Hz)
Setting = 4
50 Hz
575
100.6
23.0
0
1.3
25
50
Frequency (Hz)
Setting = 8
50 Hz
575
54.6
31.6
0
1.3 2.5
50
Frequency (Hz)
Setting = C
90 Hz
575
43.1
25.9
0
1.5 3
60
90
Frequency (Hz)
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
Characteristic
High starting torque
Constant output
Variable torque
Table 1.16 Constant Torque Characteristics, Settings 0 to 3
Setting = 1
60 Hz
575
43.1
25.9
0
1.5 3
60
Frequency (Hz)
Table 1.17 Derated Torque Characteristics, Settings 4 to 7
Setting = 5
50 Hz
575
143.8
25.9
0
1.3
25
50
Frequency (Hz)
Table 1.18 High Starting Torque, Settings 8 to B
Setting = 9
50 Hz
575
69.0
37.4
0
1.3 2.5
50
Frequency (Hz)
Table 1.19 Rated Output Operation, Settings C to F
Setting = D
120 Hz
575
43.1
25.9
0
1.5 3
60
120
Frequency (Hz)
Select high starting torque when:
• Wiring between the drive and motor exceeds 150 m.
• A large amount of starting torque is required.
• An AC reactor is installed.
Output voltage is constant when operating at greater than
60 Hz.
Used for variable torque applications. The default setting is
the same as V/f pattern Setting 7.
Setting = 2
60 Hz
575
43.1
25.9
0
1.5 3
50
60
Frequency (Hz)
Setting = 6
60 Hz
575
100.6
23.0
0
1.5
30
60
Frequency (Hz)
Setting = A
60 Hz
575
54.6
31.6
0
1.5 3
60
Frequency (Hz)
Setting = E
180 Hz
575
43.1
25.9
0
1.5 3
60
180
Frequency (Hz)
1.5 E: Motor Parameters
Application
Setting = 3
72 Hz
575
43.1
25.9
0
1.5 3
60
72
Frequency (Hz)
Setting = 7
60 Hz
575
143.8
25.9
0
1.5
30
60
Frequency (Hz)
Setting = B
60 Hz
575
69.0
43.1
0
1.5 3
60
Frequency (Hz)
Setting = F
60 Hz
575
143.8
25.9
0
1.5
30
60
Frequency (Hz)
1