YASKAWA Z1000 CIMR-ZU*A Series Programming Manual page 112

For hvac fan and pump
Hide thumbs Also See for Z1000 CIMR-ZU*A Series:
Table of Contents

Advertisement

1.8 L: Protection Functions
Fault
oC
oH1
oL1
oL2
oL3
oL4
<1> When L2-01 is set to 0 through 2 (continue operation during momentary power loss).
Use parameters L5-01 to L5-05 to set up automatic fault restart.
Set H2-01, H2-02, or H2-03 to 1E. to output a signal during fault restart.
n
L5-01: Number of Auto Restart Attempts
Sets the number of times that the drive may attempt to restart itself.
Parameter L5-05 determines the method of incrementing the restart counter. When the counter reaches the number set to L5-01,
the operation stops and the fault must be manually cleared and reset.
The restart counter is incremented at each restart attempt, regardless of whether the attempt was successful. When the counter
reaches the number set to L5-01, the operation stops and the fault must be manually cleared and reset.
The number of fault restarts is reset to zero when:
• The drive operates normally for 10 minutes following a fault restart.
• A fault is cleared manually after protective functions are triggered.
• The power supply is cycled.
No.
L5-01
n
L5-02: Auto Restart Fault Output Operation Selection
Determines if a fault output is triggered (H2-oo = E) when the drive attempts to restart.
No.
L5-02
Setting 0: No Fault Output
Run command
Fault condition
Fault display
Fault digital output
Output Frequency
(U1-02)
112
Name
Overcurrent
Drive Overheat
Motor Overload
Drive Overload
Overtorque 1
Overtorque 2
Name
Number of Auto Restart Attempts
Name
Auto Restart Fault Output Operation Selection
Auto-Restart - Cancel Early
Fault output disabled (L5-02 = 0)
Figure 1.66 Auto Restart Cancel Early
Fault
ov
PF
Uv1
STo
Setting Range
0 to 10 Times
Setting Range
L5-04
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
Name
DC Bus Overvoltage
Input Phase Loss
<1>
DC Bus Undervoltage
Pull-Out Detection
Default
0 Times
Default
0, 1
0

Advertisement