YASKAWA Z1000 CIMR-ZU*A Series Programming Manual page 27

For hvac fan and pump
Hide thumbs Also See for Z1000 CIMR-ZU*A Series:
Table of Contents

Advertisement

command
frequency
Motor speed
DC Injection Braking time is determined by the value set to b2-04 and the output frequency at the time the Run command is
removed. It can be calculated by:
Note:
If an overcurrent (oC) fault occurs during DC Injection Braking to Stop, increase the momentary power loss minimum baseblock time
(L2-03) until the fault no longer occurs.
Setting 3: Coast with Timer
When the Run command is removed, the drive will turn off its output and the motor will coast to stop. The drive will not start
if a Run command is input before the time t (C1-02) has expired. Cycle the Run command that was activated during time t
after t has expired to start the drive.
The wait time t is determined by the output frequency when the Run command is removed and by the active deceleration time.
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
Run
ON
Output
Motor coasts
Minimum Baseblock
Time (L2-03)
Figure 1.4 DC Injection Braking to Stop
DC Injection brake time
DC Injection braking time
b2-04×10
b2-04
Output frequency when
10%
Stop command was entered
Figure 1.5 DC Injection Braking Time Depending on Output Frequency
Run command
ON
Output
frequency
Figure 1.6 Coast with Timer
OFF
DC Injection Braking
with the current set in
b2-02
(b2-04) x 10 x Output frequency
=
Maximum output frequency (E1-04)
100%
(Maximum output
frequency)
OFF
ON
Drive output shut off
Run wait time t
1.2 b: Application
OFF
ON
1
27