YASKAWA Z1000 CIMR-ZU*A Series Programming Manual page 109

For hvac fan and pump
Hide thumbs Also See for Z1000 CIMR-ZU*A Series:
Table of Contents

Advertisement

n
L3-20: DC Bus Voltage Adjustment Gain
Determines the proportional gain used by overvoltage suppression (L3-11 = 1), Single Drive KEB 2 (L2-29 = 1), KEB Ride-
Thru 2 (H1-oo = 7A or 7B) ,and Intelligent Stall Prevention during deceleration (L3-04 = 2) to control the DC bus voltage.
Note:
This function is available in OLV/PM control mode.
No.
L3-20
Adjustment for Single Drive KEB 2 (L2-29 = 1) and Intelligent Stall Prevention During Deceleration
• Increase this setting slowly in steps of 0.1 if overvoltage or undervoltage occurs at the beginning of deceleration.
• Decrease this setting if there is a fair amount of speed or torque ripple.
Adjustment for Overvoltage Suppression
• Increase this setting slowly in steps of 0.1 if overvoltage suppression is enabled (L3-11 = 1) and a sudden increase in a
regenerative load causes an overvoltage fault.
• Decrease this setting if there is a fair amount of speed or torque ripple.
n
L3-21: Accel/Decel Rate Calculation Gain
Determines the proportional gain used by overvoltage suppression (L3-11 = 1), Single Drive KEB 2 (L2-29 = 1), and Intelligent
Stall Prevention during deceleration (L3-04 = 2) to calculate acceleration and deceleration rates.
No.
L3-21
Adjustment for Single Drive KEB 2 (L2-29 = 1) and Intelligent Stall Prevention During Deceleration
• Reduce L3-21 in steps of 0.05 if there is a fairly large speed or current ripple.
• Small reductions of L3-21 can help solve problems with overvoltage and overcurrent.
• Decreasing this setting too much can cause slow DC bus voltage control response and may also lengthen deceleration times
beyond optimal levels.
Adjustment for Overvoltage Suppression
• Increase this setting in steps of 0.1 if overvoltage occurs as a result of a regenerative load when overvoltage suppression is
enabled (L3-11 = 1).
• Decrease L3-21 in steps of 0.05 if there is a fairly large speed ripple when overvoltage suppression is enabled.
n
L3-24: Motor Acceleration Time for Inertia Calculations
Sets the time to accelerate the motor from stop to the maximum speed at motor rated torque. Set this parameter when using
Single Drive KEB 2 (L2-29 = 1), Intelligent Stall Prevention during deceleration (L3-04 = 2), or the overvoltage suppression
function (L3-11 = 1).
Note:
This function is available in OLV/PM control mode.
No.
L3-24
Motor Acceleration Time for Inertia Calculations
Make the calculations in the formula below:
Calculate the rated torque in the formula below:
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
Name
DC Bus Voltage Adjustment Gain
Name
Accel/Decel Rate Calculation Gain
Name
2
L3-24 =
T
[Nm] =
rated
Setting Range
Setting Range
0.00 to 200.00
Setting Range
0.001 to 10.000 s
J [kgm
2
] n
[r/min]
rated
60 T
[Nm]
rated
60
P
[kW] 10
3
Motor
2
n
[r/min]
rated
1.8 L: Protection Functions
Default
Determined by
0.00 to 5.00
A1-02
Default
Default
Determined by o2-04
1.00
1
109