YASKAWA Z1000 CIMR-ZU*A Series Programming Manual page 50

For hvac fan and pump
Hide thumbs Also See for Z1000 CIMR-ZU*A Series:
Table of Contents

Advertisement

1.2 b: Application
No.
b8-01
Setting 0: Disabled
Setting 1: Enabled
n
b8-04: Energy Saving Coefficient Value (V/f)
Fine tunes Energy Saving control. Adjust this setting while viewing the output power monitor (U1-08) and running the drive
with a light load.
A low setting results in less output voltage and less energy consumption. If the value is set too low the motor may stall. The
default setting depends on the capacity of the drive.
No.
b8-04
Note:
The default value changes if the motor rated capacity set to E2-11 is changed. The Energy Saving coefficient is set automatically when
Auto-Tuning for Energy Saving is performed.
n
b8-05: Power Detection Filter Time (V/f)
Determines how often in milliseconds the output power is measured. The Energy Saving function continuously searches out
the lowest output voltage to achieve minimum output power.
Reducing this setting increases the response time. If the filter time is too short, the motor may become unstable with a lighter
load.
No.
b8-05
n
b8-06: Search Operation Voltage Limit (V/f)
Sets the voltage limit for the Speed Search optimal output voltage detection as a percentage of the maximum output voltage.
The drive will keep the output voltage above this level during the search operation to prevent motor stalling.
Note:
If set too low, the motor may stall when the load is suddenly increased. Disabled when set to 0. Setting this value to 0 does not disable
Energy Saving.
No.
b8-06
50
Parameter Name
Energy Saving Control Selection
Name
Energy Saving Coefficient Value
Name
Power Detection Filter Time
Name
Search Operation Voltage Limit
Setting Range
Setting Range
0.00 to 655.00
Setting Range
0 to 2000 ms
Setting Range
0 to 100%
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
Default
Determined by
0, 1
A1-02
Default
Determined by
E2-11, and o2-04
Default
20 ms
Default
0%