Setting
A6
BP BAS Interlock
A7
BP Customer Safeties
A8
PI2 Disable (N.O.)
A9
PI2 Disable (N.C.)
AA
PI2 Inverse Operation
AB
PI2 Integral Reset
AC
PI2 Integral Hold
Setting 0: 3-Wire Sequence
The digital input programmed for 3-Wire control becomes the forward/reverse directional input, S1 becomes the Run command
input, and S2 becomes the Stop command input.
The drive starts the motor when the input S1 set for the Run command closes for longer than 2 ms. The drive stops the operation
when the Stop input S2 is released. When the digital input programmed for a forward/reverse operation is open, the drive is
set for forward operation. When the digital input is closed, the drive is set for reverse operation.
Note:
Input the Run and Stop commands via S1 and S2 when selecting a 3-Wire sequence.
Run command
Stop command
Forward/reverse
command
Motor speed
Note:
1. The Run command must be closed for more than 2 ms.
2. If the Run command is active at power up and b1-17 = 0 (Run command at power up not accepted), the AUTO LED will flash to indicate
that protective functions are operating. If required by the application, set b1-17 to 1 to automatically issue the Run command upon drive
power up.
WARNING! Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the correct state before applying
power to the drive. Failure to comply could result in death or serious injury from moving equipment.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly in reverse direction after power up if it is wired for 3-Wire sequence
but set up for 2-Wire sequence (default). Make sure b1-17 is set to "0" (drive does not accept a Run command active at power up). When
initializing the drive use 3-Wire initialization. Failure to comply could result in death or serious injury from moving equipment.
Settings 3 and 4: Multi-Step Speed Reference 1 and 2
Switches multi-step speed frequency references d1-01 to d1-04 by digital inputs.
56
for details.
Setting 6: Jog Reference Selection
The Jog frequency set in parameter d1-17 becomes the frequency reference when the input terminal closes.
Frequency Reference on page 56
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
Function
Stop Switch
Run Switch
(N.C.)
(N.O.)
Figure 1.30 3-Wire Sequence Wiring Diagram
2 ms min.
Can be either ON or OFF
OFF (forward)
S
o t
p
Forward
Figure 1.31 3-Wire Sequence
for details.
Page
Setting
81
AD
Select PI2 Parameters
81
AE
BP Bypass Run
81
AF
Emergency Override Forward Run
81
B0
Emergency Override Reverse Run
81
B1
Customer Safeties
81
B2
BAS Interlock
82
DRIVE
S1
Run Command (Runs when Closed)
S2
Stop Command (Stops when Open)
S5
FWD/REV (Multi-Function Input)
(H1-05 = 0)
SN
Standard Digital Input Common
2 ms min.
ON (reverse)
R
e
v
e
s r
e
S
o t
p
Refer to d1: Frequency Reference on page
1.7 H: Terminal Functions
Function
Can be
ON or OFF
Forward
Refer to d1:
Page
82
82
82
82
82
82
1
73

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cimr-zu series

Table of Contents