5-3-6
I/O Module Calibration
accuracy of ADAM module. There are several modes for module's
calibration: Zero calibration, Span calibration, CJC calibration, and
Analog Output calibration. Only analog input and out- put modules can
be calibrated, includes ADAM-5013, 5017, 5017H, 5018 and 5024.
Zero Calibration
1. Apply power to the module and let it warm up for 30 minutes.
2. Make sure the module is correctly installed and properly configured
for the input range you want to calibrate.
3. Use a precision voltage source to apply a calibration voltage to the V+
and V- terminals of the ADAM-5013, 5017, 5017H, and 5018 modules.
4. Click the Execute button.
Span Calibration Follow the same procedure of zero calibration and
click the Execute but- ton.
ADAM-5000/TCP User's Manual
System Hardware Configuration
Figure 5-17: Zero Calibration
Figure 5-18: Span Calibration
Chapter 5
Calibration is to adjust the
5-15