Advantech ADAM-5000/TCP Series Manual page 283

Distributed da&c system based on ethernet
Table of Contents

Advertisement

Chapter 6
@aaSiCjG
Name
Description
Syntax
Response
Example
}
6-170
ADAM-5000/TCP User's Manual
Planning Your Application Program
Read Initial Counter
Read initial counter value of specified module.
@aaSiCjG(cr)
@ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadeci-
mal address of the ADAM-5000/TCP system.
SiCj identifies the I/O slot i and the channel j for the
module you want to return a prior value. G is the last
value readback command.
(cr) is the terminating character, carriage return (0Dh)
!aa(data)(cr) if the command is valid.
?aa(cr) if an invalid operation was entered. There is
no response if the module detects a syntax error or
communication error or if the specified ad- dress
does not exist.
! delimiter character indicating a valid command was
received.
? delimiter character indicating the command was in-
valid.
aa (range 00-FF) represents the 2-character hexadeci-
mal address of an ADAM-5000/TCP system.
(data) is initial value from 0 to 4294967295.Be aware
that (data) has 10 characters.
(cr) is the terminating character, carriage return (0Dh)
command: @01S3C2G(cr)
response: !010000004369(cr)
The channel 2 of ADAM-5080 in slot 3 in ADAM-
5000/TCP system at address 01h is instructed to re-
turn counter initial value. The initial counter value is
4369.