Planning Your Application Program
Note:
the output for an analog input alarm, it cannot be reconfigured
via digital output commands. Channels used for analog input
alarms
always have a higher priority.
ADAM-5000/TCP User's Manual
01h. Channels 2, 4, 5, 9 and 12 will be set to ON, and
all other channels are set to OFF.
command: #01S0003A(cr)
response: >(cr) An output byte with value 3Ah
(00111011) is sent to the digital output module
(ADAM-5060) in slot 0 of the ADAM-5000/TCP
system at address 01h. Chan- nels 0, 1, 3, 4 and 5 will
be set to ON while channel 2 is set to OFF.
Bits 6 and 7 are not used and always default to 0.
If any channel of the digital output module is configured as
Chapter 6
6-145