Planning Your Application Program
Example
Note:
An analog input module requires a maximum of 2 seconds after
it receives a Set Alarm Limit command to let the settings take
effect. During this interval, the module cannot be addressed to
perform any other actions.
ADAM-5000/TCP User's Manual
command: $01S0C1AHU+080.00(cr)
response: !01(cr)
Channel 1 of slot 0 in the ADAM-5000/TCP system
at address 01h is configured to accept type-T ther-
mocouple input. The command will set its High alarm
limit to +80°C.
The system confirms the command has
been re- ceived.