Table 6-8 Analog Input Alarm Command Set Table - Advantech ADAM-5000/TCP Series Manual

Distributed da&c system based on ethernet
Table of Contents

Advertisement

Chapter 6
Planning Your Application Program
Analog Input Alarm Command Set
Command
Syntax
$aaSiCjAhs
$aaSiCjAh
$aaSiCjAhEs
$aaSiCjCh
$aaSiCjAhCSk-
Cn
$aaSiCjRhC
$aaSiCjAhU(da-
ta)
$aaSiCjRhU
$aaSiCjS

Table 6-8 Analog Input alarm command set table

Note: This command set applies to the ADAM-5013,
ADAM-5017, ADAM-5017H/5017UH and the ADAM-5018 .
6-108
ADAM-5000/TCP User's Manual
Command
Name
Set Alarm Mode
Read Alarm
Mode
Enable/Disable
Alarm
Clear Latch
Alarm
Set Alarm
Connection
Read Alarm
Connection
Set Alarm Limit Sets the High/Low alarm limit
Read Alarm
Limit
Read Alarm
Status
Description
Sets the High/Low alarm in either
Momentary or Latching mode
Returns the alarm mode for the
specified channel.
Enables or Disables the High/Low
alarm of the specified channel
Resets a latched alarm
Connects the High/Low alarm of a
specified input channel to a
specified digital output channel
Returns the alarm limit output
connection of a specified input
channel
value for the specified input
channel
Returns the High/Low alarm limit
value for the specified input
channel
Reads whether an alarm occurred
for a specified input channel