Chapter 6
Planning Your Application Program
(dddd) is the input value in two's complement format
of the interrogated module of the specified system.
The (dddd) from all channels is shown in sequence
from 7 to 0. If (dddd)=" ", it means the channel is
invalid.
(cr) is the terminating character, carriage return (0Dh).
Example
command: #01S3(cr)
response: +6.000 +7.000 +8.125 +4.250
+10.000 +8.500 +7.675 +5.445 (cr) The command
requests the ADAM-5017H/5017UH module in slot
3 of the ADAM-5000/TCP system at address 01h to
return the input values of all channels. The analog
input module responds with the input values of all
channels, in sequence from 0 to 7: +6.000,
+7.000, +8.125, +4.250, +10.000, +8.500, +7.675,
+5.445.
6-86
ADAM-5000/TCP User's Manual