Advantech ADAM-5000/TCP Series Manual page 127

Distributed da&c system based on ethernet
Table of Contents

Advertisement

Chapter 6
Planning Your Application Program
$aaSi1
Name
Description
Syntax
Response
6-60
ADAM-5000/TCP User's Manual
RTD Zero Calibration
Calibrates a specified RTD input module of a speci-
fied system to correct for offset errors.
$aaSi1(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadeci-
mal address of the ADAM-5000/TCP system which
contains the module which is to be calibrated.
Si identifies the slot i (i:0 to 7) containing the RTD
module to be calibrated.
1 represents the zero calibration command.
(cr) is the terminating character, carriage return (0Dh).
!aa(cr) if the command is valid.
?aa(cr) if an invalid operation was entered. There is
no response if the module detects a syntax error or
communication error or if the specified ad- dress
does not exist.
! delimiter character indicating a valid command was
received.
? delimiter character indicating the command was in-
valid.
aa (range 00-FF) represents the 2-character hexadeci-
mal address of an ADAM-5000/TCP system.
(cr) is the terminating character, carriage return (0Dh).