Appendix B

B.5 Analog Output Formats

output modules to receive data from the host in Engineering Units.
Engineering Units Data can be represented in engineering units by
setting bits 0 and 1 of the data format/checksum/integration time
parameter to 0.
This format presents data in natural units, such as milliamps. The
Engineering Units format is readily parsed by the majority of computer
languages as the total data string length is fixed at six characters: two
decimal digits, a decimal point and three decimal digits. The resolution
is 5 µA.
Example: An analog output module on channel 1 of slot 0 in an
ADAM-5000 system at address 01h is configured for a 0 to 20 mA
range. If the output value is +4.762 mA, the format of the Analog
Data Out com- mand would be #01S0C14.762<cr>

B.6 Analog Output Ranges

Range Code
30
31
32
B-9
ADAM-5000/TCP User's Manual
Data Formats and I/O Ranges
Output Range Data Formats
Description
Engineedring Units
% of Span
0 to 20 mA
Hexadecimal
Binary
Engineedring Units
% of Span
4 to 20 mA
Hexadecimal
Binary
Engineedring
Units
% of Span
0 to 10 V
Hexadecimal
Binary
You can configure ADAM analog
Minimum
Maximum
Specified
Specified
Signal
Signal
20.000
00.000
+100.00
+000.00
FFF
20.000
04.000
+100.00
+000.00
FFF
10.000
00.000
+100.00
+000.00
FFF
Displayed
Resolution
5 µA
5 µA
000
5 µA
5 µA
5 µA
000
5 µA
2.442 mV
2.442 mV
000
2.442 mV