Programming the PFC with WAGO-I/O-PRO CAA

I/O config

Under the link I/O config you can view the configuration or the write access
rigths on the outputs of your fieldbus node.
In the left window of this web page is displayed the node configuration
generated with the hardware configurator "WAGO-I/O-PRO CAA I/O
Configurator". If no modules are indicated in this window, then no hardware
configuration and also no assignment from write access rights is still taken
place.
In this case, always fieldbus 1, that means Modbus_TCP (Default), has the r
write access rigths on the outputs.
More Information
Please, find detailed information about the WAGO-I/O-PRO CAA I/O-
Configurator in chapter 3.1.7 "Starting up an ETHERNET TCP/IP fieldbus
node".
In the right window of this web page is displayed the physical node
configuration and the current process values, if the file 'genIOconf.xml' was
generated. A condition for the file generation is, that on the web page reached
by the link "Features ", the function " Generate file 'genIOconf.xml' " was
activated. On delivery this function is deactivated by default, so that the file
' genIOconf.xml ' is not generated and no modules and process data are
represented in this window.