Fieldbus Controller 750-841
Programming the PFC with WAGO-I/O-PRO CAA
11. You can change now the access authorization, if for individual modules, the
12. When you have completed the assignments, you can start programming with
More information
For a detailed description on how to use the software WAGO-I/O-PRO CAA
and the I/O-Configurator, please refer to the Online-Help of WAGO-I/O-PRO
CAA.
Note
Alternatively, the "EA-config.xml" file can be created with each editor and
then be transported via FTP in the Controller directory "/etc".
The configuration with the "EA-config.xml" file, which is already stored in
the controller, is described in the following chapter.
write access should be via the fieldbus (MODBUS TCP/IP or Ethernet/IP).
For each module added, the write access first is fixed from the PLC.
You can change it by determining in the right-hand dialogue
window/register "Module parameters for each individual module, from
where the write access on the I/O Module data should take place.
For this in the "Value" column. your options include:
- PLC (The PFC controls its I/O locally)
- fieldbus 1 (A MODBUS TCP Fieldbus Master controls the I/O module)
- fieldbus 2 (An Ethernet IP Fieldbus Master controls the I/O module)
the IEC 61131-3 program tool. The configuration file "EA-config.xml" is
generated as soon as you compile the project.