196 •
Ethernet/IP (Ethernet/Industrial Protocol)
Object model
Instance 198 (C6
This instance is used to establish a connection when no outputs are to be
addressed or when inputs, which are already being used in an exclusive owner
connection, are to be interrogated . The data length of this instance is always
zero.
This instance can only be used in the "consumed path" (seen from the slave
device).
Instance 199 (C7
This instance is used to establish a connection based on an existing exclusive
owner connection. The new connection also has the same transmission
parameters as the exclusive owner connection. When the exclusive owner
connection is cleared, this connection, too, is automatically cleared. The data
length of this instance is always zero.
This instance can only be used in the "consumed path" (from the point of view
of the slave device).
Common Services
Service code
0E hex
10 hex
) „Input Only"
hex
)
hex
Service available
Service Name
Class
Instance
yes
yes
Get_Attribute_Single
no
yes
Set_Attribute_Single
Description
Supplies contents of the appropriate attribute
Modifies an attribute value