PLC

Under the PLC link you can define the status of the outputs, if your
application program stops.
If there is a checkmark in the small box behind "Enabled", all outputs are set
to zero, otherwise the outputs remain to the last current value.

Features

Under the link Features you can get the HTML page "Feature" on that you
can activate or deactivate additional functions.
With the function " Autoreset on system error " an automatic Software Reset
in the case of an arising system error is possible.
This function can ensure a safe and durable operation with use within
difficulty accessible ranges (e.g. within the offshore range). The automatic
reset releases, as soon as the controller is in an error status, which requires a
reset.
On delivery this function is deactivated (default), then with the arising of an
error the diagnosis is signalled by the blink code of the "I/O" LED. After the
evaluation of the blink code and the error removal, then a manual reset is to be
accomplished.
With the function " Generate file 'genIOconf.xml' " it is possible to generate
an IO configuration file, which contains beside the real fieldbus node
configuration also an access mechanism on process values.
On delivery this function is deactivated (default). With the activation of this
function, the configuration file is new generated with each Power On. The file
content is then represented in the right window of the web page you can get
under the link "IO config".