Bootp Table - WAGO 750 Series Manual

Modular i/o-system; ethernet tcp/ip
Hide thumbs Also See for 750 Series:
Table of Contents

Advertisement

You can download a free copy of the WAGO's BootP server over the Internet
under at http://www.wago.com/-
"Service"/"Downloads"/"Software"/"ELECTRONICC"/-
'WAGO BootPServer V1.0 Windows 95/NT - ZIP Archiv'.
Note
The IP address can be allocated under other operating systems (e.g. under
Linux) as well as with any other BootP servers.
Attention
The IP address can be allocated in a direct connection via a crossover cable or
via a parallel cable and a hub. An allocation over a switch is not possible.

BootP table

Note
A prerequisite for the following steps is the correct installation of the WAGO
BootP server.
1. To start the BootP server, click on the Start menu item Programs/WAGO
2. After the BootP Server is started, click on the Edit Bootptab button
Fig. 3-12: BootP table
The examples mentioned above contain the following information:
Declaration
node1,
node2
ht=1
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
Starting up an ETHERNET TCP/IP fieldbus node
Software/WAGO BootP Server.
located on the right hand side of the display. An editable file will appear in
Windows NotePad (bootptab.txt). This file is a database for the BootP
server. The file contains two examples for the allocation of an IP address,
the example commands are directly after the following comment lines:
- "Example of entry with no gateway"
- "Example of entry with gateway"
Meaning
Any name can be given for the node here.
Specify the hardware type of the network here.
The hardware type for ETHERNET is 1.
Fieldbus Controller 750-841
• 85
p012908d