Technical Data - WAGO 750 Series Manual

Modular i/o-system; ethernet tcp/ip
Hide thumbs Also See for 750 Series:
Table of Contents

Advertisement

6 •
The WAGO-I/O-SYSTEM 750

Technical Data

2.2 Technical Data
Mechanic
Material
Dimensions
- Coupler / Controller
- I/O module, single
- I/O module, double
Installation
modular by
Mounting position
Length of entire node
Marking
Wire range
Wire range
Contacts
Power jumpers contacts
Current via power contacts
Voltage drop at I
Data contacts
Climatic environmental conditions
Operating temperature
Storage temperature
Relative humidity
Resistance to harmful substances
Maximum pollutant concentration at
relative humidity < 75%
Special conditions
Polycarbonate, Polyamide 6.6
- 51 mm x 65* mm x 100 mm
- 12 mm x 64* mm x 100 mm
- 24 mm x 64* mm x 100 mm
* from upper edge of DIN 35 rail
on DIN 35 with interlock
double featherkey-dovetail
any position
≤ 831 mm
marking label type 247 and 248
paper marking label 8 x 47 mm
CAGE CLAMP® Connection
0,08 mm² ... 2.5 mm²
AWG 28-14
8 – 9 mm Stripped length
blade/spring contact
self-cleaning
10 A
max
< 1 V/64 modules
max
slide contact, hard gold plated
1,5µm, self-cleaning
0 °C ... 55 °C
-20 °C ... +85 °C
5% to 95 % without condensation
acc. To IEC 60068-2-42 and IEC 60068-2-43
SO
S ≤ 10 ppm
H
2
Ensure that additional measures for components are
taken, which are used in an environment involving:
– dust, caustic vapors or gasses
– ionization radiation.
≤ 25 ppm
2