Appendix A
Default Values and Ranges
A.1

Overview

This appendix provides information on the default values for most transmitter parameters. Where
appropriate, valid ranges are also defined.
These default values represent the transmitter configuration after a master reset. Depending on how
the transmitter was ordered, certain values may have been configured at the factory.
The default values listed here apply to all Version 5.0 transmitters using a Version 3.2 enhanced core
processor.
A.2

Most frequently used defaults and ranges

The table below contains the default values and ranges for the most frequently used transmitter
settings.
Table A-1
Transmitter default values and ranges
Type
Setting
Flow
Flow direction
Flow damping
Flow calibration factor
Mass flow units
Mass flow cutoff
Volume flow type
Volume flow units
Volume flow cutoff
Configuration and Use Manual
Default
Range
Forward
0.8 sec
0.0–51.2 sec
1.00005.13
g/s
0.0 g/s
Liquid
L/s
0.0 L/s
0.0–x L/s
Comments
User-entered value is
corrected to nearest lower
value in list of preset values.
For gas applications, Micro
Motion recommends a value
of 3.2.
For T-Series sensors, this
value represents the FCF and
FT factors concatenated. See
Section 6.2.2.
Recommended setting:
• Standard use – 0.2% of the
sensor's rated maximum
flowrate
• Empty-full-empty batching –
2.5% of the sensor's
maximum flowrate
x is obtained by multiplying
the flow calibration factor by
0.2, using units of L/s.