Danfoss VLT AQUA Drive FC 202 Design Manual page 185

110-1400 kw
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

General Specifications and ...
1)
Max. terminal load (DC-13)
on 4-5 (NO) (Inductive load)
1)
Max. terminal load (AC-1)
on 4-6 (NC) (Resistive load)
on 4-6 (NC) (Inductive load @ cosφ 0.4)
Max. terminal load (AC-15)
1)
1)
Max. terminal load (DC-1)
on 4-6 (NC) (Resistive load)
1)
Max. terminal load (DC-13)
on 4-6 (NC) (Inductive load)
Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO)
Environment according to EN 60664-1
1) IEC 60947 parts 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2) Overvoltage Category II
3) UL applications 300 V AC 2 A
Control card, 10 V DC output
Terminal number
Output voltage
Max. load
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control characteristics
Resolution of output frequency at 0-590 Hz
System response time (terminals 18, 19, 27, 29, 32, 33)
Speed control range (open loop)
Speed accuracy (open loop)
All control characteristics are based on a 4-pole asynchronous motor
Surroundings
Enclosure type D1h/D2h/E1/E2
Enclosure type D3h/D4h
Enclosure type D1h/D2h, E1, F1-F4, F8-F13
Vibration test enclosure D/E/F
Maximum relative humidity
Aggressive environment (IEC 721-3-3), coated
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature (at 60 AVM switching mode)
Maximum ambient temperature with reduced load
Derating for high ambient temperature, see chapter 8.5.5 Derating for Ambient Temperature
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Maximum altitude above sea level with derating
Derating for high altitude, see chapter 8.5 Special Conditions
EMC standards, Emission
EMC standards, Immunity
See chapter 8.5 Special Conditions for more information.
Control card performance
Scan interval
Control card, USB serial communication
USB standard
USB plug
MG20Z202
Design Guide
5% - 95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
Danfoss A/S © Rev. 06/2014 All rights reserved.
24 V DC 10 mA, 24 V AC 20 mA
overvoltage category III/pollution degree 2
1:100 of synchronous speed
30–4000 rpm: Maximum error of ±8 rpm
IP21/Type 1, IP54/Type 12
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EN 61800-3, EN 61000-6-1/2,
USB type B "device" plug
24 V DC, 0.1A
240V AC, 2 A
240V AC, 0.2A
50 V DC, 2 A
24 V DC, 0.1 A
50
10.5 V ± 0.5 V
25 mA
± 0.003 Hz
8
8
≤ 2 ms
IP00/chassis
IP20/chassis
1 g
class 3C3
Max. 45 °C
55 °C
0 °C
- 10 °C
-25 - +65/70 °C
1000 m
3000 m
5 ms
1.1 (Full speed)
183