Danfoss VLT AQUA Drive FC 202 Design Manual page 191

110-1400 kw
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

General Specifications and ...
CAUTION
Alarms that are trip-locked offer additional protection,
meaning that the mains supply must be switched off
before the alarm can be reset. After switching mains
supply back on, the frequency converter is no longer
blocked and may be reset as described above once the
cause has been rectified.
Alarms that are not trip-locked can also be reset using
the automatic reset function in 14-20 Reset Mode
(Warning: automatic wake-up is possible)
If a warning and alarm is marked against a code in
Table 8.25, this means that either a warning occurs
before an alarm, or it can be specified whether it is a
warning or an alarm that is to be displayed for a given
fault.
This is possible, for instance, in 1-90 Motor Thermal
Protection. After an alarm or trip, the motor carries on
coasting, and the alarm and warning flash on the
frequency converter. Once the problem has been
rectified, only the alarm continues flashing.
No. Description
1
10 Volts low
2
Live zero error
3
No motor
4
Mains phase loss
5
DC link voltage high
6
DC link voltage low
7
DC over voltage
8
DC under voltage
9
Inverter overloaded
10
Motor ETR over temperature
11
Motor thermistor over temperature
12
Torque limit
13
Over Current
14
Earth fault
15
Hardware mismatch
16
Short Circuit
17
Control word timeout
18
Start failed
23
Internal Fan Fault
24
External Fan Fault
25
Brake resistor short-circuited
26
Brake resistor power limit
27
Brake chopper short-circuited
28
Brake check
29
Drive over temperature
30
Motor phase U missing
31
Motor phase V missing
32
Motor phase W missing
33
Inrush fault
34
Fieldbus communication fault
35
Out of frequency range
36
Mains failure
MG20Z202
Design Guide
NOTICE
No missing motor phase detection (no 30-32) and no
stall detection is active when 1-10 Motor Construction is
set to [1] PM non salient SPM.
Warning
Alarm/Trip
X
(X)
(X)
(X)
(X)
(X)
X
X
X
X
X
X
X
X
(X)
(X)
(X)
(X)
X
X
X
X
X
X
X
X
(X)
(X)
X
X
X
X
(X)
(X)
X
X
(X)
(X)
X
X
(X)
(X)
(X)
(X)
(X)
(X)
X
X
X
X
X
X
X
Danfoss A/S © Rev. 06/2014 All rights reserved.
Alarm/Trip Lock
Parameter Reference
6-01
1-80
(X)
14-12
1-90
1-90
X
X
X
X
8-04
14-53
2-13
2-15
X
(X)
4-58
(X)
4-58
(X)
4-58
X
8
8
189