Introduction
To document immunity against electrical interference from
electrical phenomena, the following immunity tests have
been made on a system consisting of a frequency
2
2
converter (with options if relevant), a screened control
cable and a control box with potentiometer, motor cable,
and motor.
The tests were performed in accordance with the following
basic standards:
EN 61000-4-2 (IEC 61000-4-2): Electrostatic
discharges (ESD): Simulation of electrostatic
discharges from human beings.
EN 61000-4-3 (IEC 61000-4-3): Incoming electro-
magnetic field radiation, amplitude modulated
simulation of the effects of radar and radio
Voltage range: 380-480 V, 525-600 V, 525-690 V
Basic standard
Acceptance criterion
Line
Motor
Brake
Load sharing
Control wires
Standard bus
Relay wires
Application and Fieldbus
options
LCP cable
External 24V DC
Enclosure
Table 2.18 EMC Immunity Form
1) Injection on cable shield
AD: Air Discharge
CD: Contact Discharge
CM: Common mode
DM: Differential mode
34
Design Guide
Burst
Surge
IEC 61000-4-4
IEC 61000-4-5
B
B
2 kV/2Ω DM
4 kV CM
4 kV/12Ω CM
4 kV CM
4 kV/2Ω
1)
4 kV CM
1)
4 kV/2Ω
4 kV CM
1)
4 kV/2Ω
2 kV CM
2 kV/2Ω
1)
2 kV CM
2 kV/2Ω
1)
2 kV CM
1)
2 kV/2Ω
2 kV CM
1)
2 kV/2Ω
2 kV CM
2 kV/2Ω
1)
0.5 kV/2Ω DM
2 V CM
1 kV/12Ω CM
Danfoss A/S © Rev. 06/2014 All rights reserved.
communication equipment as well as mobile
communications equipment.
EN 61000-4-4 (IEC 61000-4-4): Burst transients:
Simulation of interference brought about by
switching a contactor, relay, or similar devices.
EN 61000-4-5 (IEC 61000-4-5): Surge transients:
Simulation of transients brought about for
example, by lightning that strikes near instal-
lations.
EN 61000-4-6 (IEC 61000-4-6): RF Common
mode: Simulation of the effect from radio-
transmission equipment joined by connection
cables.
See Table 2.18.
ESD
Radiated electromagnetic
IEC
field
61000-4-2
IEC 61000-4-3
B
A
8 kV AD
10V/m
6 kV CD
RF common
mode voltage
IEC 61000-4-6
A
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS