How to Install
Input Polarity of Control Terminals
PNP (Source)
Digital input wiring
12
13
18
19
27
Illustration 5.56 Input Polarity of Control Terminals
NPN (Sink)
Digital input wiring
12
13
18
19
27
Illustration 5.57 Input Polarity of Control Terminals
MG20Z202
Design Guide
29
32
33
20
37
29
32
33
20
37
Danfoss A/S © Rev. 06/2014 All rights reserved.
5.3.16 Switches S201, S202 and S801
Switches S201 (A53) and S202 (A54) are used to select a
current (0–20 mA) or a voltage (0–10 V) configuration of
the analog input terminals 53 and 54 respectively.
Switch S801 (BUS TER.) can be used to enable termination
on the RS-485 port (terminals 68 and 69).
See Illustration 5.51 and Illustration 5.52.
Default setting:
S201 (A53) = OFF (voltage input)
S202 (A54) = OFF (voltage input)
S801 (Bus termination) = OFF
NOTICE
Change switch position at power off only.
Illustration 5.58 Switch Locations