How to Install
connecting one end of the screen to earth via a
100 nF capacitor (keeping leads short).
e.
Cables for serial communication
Eliminate low-frequency noise currents between
two frequency converters by connecting one end
of the screen to terminal 61. This terminal is
connected to earth via an internal RC link. Use
twisted-pair cables for reducing the differential
mode interference between the conductors.
5
5
138
Design Guide
PLC etc.
PLC etc.
PLC etc.
PLC etc.
PE
69
68
Illustration 5.99 Earthing
Danfoss A/S © Rev. 06/2014 All rights reserved.
PE
PE
PE
PE
PE
PE
PE
Min. 16mm
Equalizing cable
PE
100nF
FC
61
PE
FC
a
FC
PE
b
FC
c
2
FC
d
FC
68
69
e
MG20Z202