2.5.1 I/O Module Setting Check after Changing EW Board Station Number Setting

2
Setup
2.5
System Configuration
The EW board removal and station number change performed in the
chapter 2.4 "Connection of Welding Power Source and YRC1000"
changes the I/O module setting. The setting changes must be recognized
with [Setting] in the maintenance mode.
1. Start the YRC1000 while pressing [MAIN MENU]
– Start the YRC1000 in maintenance mode.
2. Select {SYSTEM} → {SECURITY} → "MANAGEMENT MODE".
– A password must be entered after selecting "MANAGEMENT
MODE".
3. Select {SYSTEM} → {SETUP} → "IO MODULE".
4. Press the [Enter] key to check the I/O module connection status.
– If no EW board is connected, the board column displays "NONE" as
follows.
5. A confirmation dialog box appears. Select {YES}.