Configure process measurement
Result:
4.2
Configure volume flow measurement for liquid
applications
The volume flow measurement parameters control how liquid volume flow is measured
and reported.
Restriction
You cannot implement both liquid volume flow and gas standard volume flow at the same time.
Choose one or the other.
Note
If you need to switch from gas standard volume to liquid volume, polling for base density will
automatically be disabled.
4.2.1

Configure Volume Flow Type for liquid applications

ProLink III
Field Communicator Configure > Manual Setup > Measurements > GSV > Volume Flow Type > Liquid
Overview
Volume Flow Type controls whether liquid or gas standard volume flow measurement will
be used.
Restriction
Gas standard volume measurement is incompatible with some applications. Set Volume Flow Type
to Liquid if you are using any of the following applications:
Procedure
Set Volume Flow Type to Liquid.
22
Mass Flow Cutoff: 10 g/sec
If the mass flow rate drops below 15 g/sec but not below 10 g/sec:
-
The mA Output will report zero flow.
-
The Frequency Output will report the actual flow rate, and the actual flow rate
will be used in all internal processing.
If the mass flow rate drops below 10 g/sec, both outputs will report zero flow, and 0
will be used in all internal processing.
Device Tools > Configuration > Process Measurement > Flow
Production Volume Reconciliation (PVR)
Micro Motion Model 1500 Transmitters with Analog Outputs