Emerson Micro Motion 1500 Configuration And Use Manual page 60

Transmitters with analog outputs
Hide thumbs Also See for Micro Motion 1500:
Table of Contents

Advertisement

Configure device options and preferences
Status alerts and options for Status Alert Severity
Table 5-2:
Status alerts and Status Alert Severity
Alert code
Status message
A001
EEPROM Error
A002
RAM Error
A003
No Sensor Response
A004
Temperature Overrange
A005
Mass Flow Rate Overrange
A006
Characterization Required
A008
Density Overrange
A009
Transmitter Initializing/
Warming Up
A010
Calibration Failure
A011
Zero Calibration Failed:
Low
A012
Zero Calibration Failed:
High
A013
Zero Calibration Failed:
Unstable
A014
Transmitter Failure
A016
Sensor RTD Failure
A017
T-Series RTD Failure
A018
EEPROM Error (Transmit-
ter)
A019
RAM Error (Transmitter)
A020
No Flow Cal Value
A021
Incorrect Sensor Type (K1)
A022
Configuration Database
Corrupt (Core Processor)
A023
Internal Totals Corrupt
(Core Processor)
A024
Program Corrupt (Core
Processor)
A025
Boot Sector Fault (Core
Processor)
A026
Sensor/Transmitter Com-
munications Failure
A028
Core Processor Write Fail-
ure
54
Default severity Notes
Fault
Fault
Fault
Fault
Fault
Fault
Fault
Fault
Fault
Fault
Fault
Fault
Fault
Fault
Fault
Fault
Fault
Fault
Fault
Fault
Applies only to flowmeters with the
standard core processor.
Fault
Applies only to flowmeters with the
standard core processor.
Fault
Applies only to flowmeters with the
standard core processor.
Fault
Applies only to flowmeters with the
standard core processor.
Fault
Fault
Micro Motion Model 1500 Transmitters with Analog Outputs
Configurable?
No
No
Yes
No
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
No
Yes
Yes
No
No
Yes
No
No
No
No
No
No
No