Emerson Micro Motion 1500 Configuration And Use Manual page 87

Transmitters with analog outputs
Hide thumbs Also See for Micro Motion 1500:
Table of Contents

Advertisement

Procedure
1.
2.
Configure burst parameters
ProLink III
Field Communicator Configure > Manual Setup > Inputs/Outputs > Communications > Set Up Burst Mode
Overview
Burst mode is a mode of communication during which the transmitter regularly
broadcasts HART digital information over the mA Output. The burst parameters control
the information that is broadcast when burst mode is enabled.
Tip
In typical installations, burst mode is disabled. Enable burst mode only if you are using a HART
Triloop.
Procedure
1.
Configuration and Use Manual
Set HART Address to a value that is unique on your network.
Default: 0
Range: 0 to 15
Tips
The default address is typically used unless you are in a multidrop environment.
Devices using HART protocol to communicate with the transmitter may use either HART
Address or HART Tag (Software Tag) to identify the transmitter. Configure either or both,
as required by your other HART devices.
Ensure that mA Output Action is configured appropriately.
Option
Description
Enabled (Live)
The primary mA Output reports process data as configured.
Disabled (Fixed)
The primary mA Output is fixed at 4 mA and does not report process
data.
Important
If you use ProLink III to set HART Address to 0, the program automatically enables mA Output
Action. If you use ProLink III to set HART Address to any other value, the program
automatically disables mA Output Action. This is designed to make it easier to configure the
transmitter for legacy behavior. Always verify mA Output Action after setting HART Address.
Device Tools > Configuration > Communications > Communications (HART)
Enable Burst Mode.
Integrate the meter with the control system
81