Analog Value Preprocessing - Siemens SIMATIC TeleControl DNP3 Configuration Manual

Hide thumbs Also See for SIMATIC TeleControl DNP3:
Table of Contents

Advertisement

Table 3- 5
(calculation cycle)
With the change in the process value shown in the example, the threshold value trigger
configured with 2.0 is initiated twice:
● At the time 3.5 s: The value of the integrated deviation is at 2.0. The new process value
stored in the send buffer is 20.5.
● At the time 6.0 s: The value of the integrated deviation is at 2.1. The new process value
stored in the send buffer is 19.9.
In this example, if a deviation of the process value of approximately 0.5 should fire the
trigger, then with the behavior of the process value shown here a threshold value of
approximately 1.5 ... 2.5 would need to be configured.
3.20.9

Analog value preprocessing

The TIM supports analog value preprocessing. For analog value data points, some or all of
the functions described below can be configured.
Requirements and restrictions
You will find the requirements for the configuration of the preprocessing options and
restrictions in the section relating to the particular function.
Note
Restrictions due to configured triggers
The analog value preprocessing options "Error suppression time", "Limit value calculation"
and "smoothing" are not performed if no threshold value trigger is configured for the relevant
data point.. In these cases, the read process value of the data point is entered in the image
memory and transferred transparently before the preprocessing cycle of the threshold value
calculation (500 ms) elapses.
Configuration - DNP3
Configuration Manual, 11/2018, C79000-G8976-C508-01
Example of the integration calculation of a threshold value configured with 2.0
Time [s]
Process value
stored in the
send buffer
0
20.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
20.5
4.0
4.5
5.0
5.5
6.0
19.9
Current process
Absolute deviation
value
from the stored
20.0
20.3
19.8
20.2
20.5
20.3
20.4
20.5
20.4
20.1
19.9
20.1
19.9
Configuration
3.20 Configuring data points
Integrated devia-
tion
value
0
0
+0.3
0.3
-0.2
0.1
+0.2
0.3
+0.5
0.8
+0.3
1.1
+0.4
1.5
+0.5
2.0
-0.1
-0.1
-0.4
-0.5
-0.6
-1.1
-0.4
-1.5
-0.6
-2.1
119