3.20 Configuring data points
Set limit value 'low' / Set limit value 'high'
Requirements for the function
● Configuration of the threshold trigger for this data point
● PLC tag in the bit memory operand area or data area
The analog value data point must be linked to a PLC tag in the memory or data area
(data block).
For PLC tags for analog input modules (input operand area) limit value configuration is
not possible. With these analog values the limit values of the following table are used
automatically.
The configuration of limit values is pointless for measured values that have already been
preprocessed on the CPU.
Function
In these two input boxes, you can set a limit value in the direction of the start of the
measuring range or in the direction of the end of the measuring range.
You can also evaluate the limit values, for example as the start or end of the measuring
range.
Configuration of the limit value
The limit value is configured as a whole decimal number. The range of values is based on
the range of values of the raw value of analog input modules.
Please note: The entry of the value 0 (zero) is interpreted as a deactivated limit value.
Range
Overflow
Overrange
Nominal range
(unipolar / life zero)
Nominal range (bipolar)
Underrange
(unipolar / life zero)
Underrange (bipolar)
Undershoot / wire break
124
Value of the 16-bit PLC variable *
Decimal
Hexadecimal
32767
7FFF
32511
7EFF
...
...
27649
6C01
27648
6C00
...
...
0
0000
27648 ...
6C00 ...
0
0000
... -27648
... 9400
-1
FFFF
...
...
-4864
ED00
-27649
93FF
...
...
-32512
8100
-32768
8000
Module output [mA]
0 .. 20
-20 .. +20
(unipolar)
(bipolar)
> 23.515
> 23.515
23.515
23.515
...
...
20.001
20.001
20
...
0
20 ...
0
... -20
-0.001
...
-3.518
-20.001
...
-23.516
< -3.518
Configuration Manual, 11/2018, C79000-G8976-C508-01
Measuring
range [%]
4 .. 20
(life zero)
> 22.810
> 117.593
22.810
117.593
...
...
20.001
100.004
20
100
...
...
4
0
100 ...
0
... -100
3.999
-0.004
...
...
1.185
-17.59
-100.004
...
-117.593
< 1.185
< -17.593