Coding Of The Analog Values And Measured Value Ranges - Siemens Add 7 AddFEM Manual

Front end module
Table of Contents

Advertisement

AddFEM
4.3.4

Coding of the Analog Values and Measured Value Ranges

Analog value representation for asymmetric (unipolar) measuring ranges:
System
Value
118.507%
117.596%
117.582%
100%
0.014468%
0%
–17.593%
–118.522%
System
Value
118.507%
117.593%
117.589%
100%
0.014468%
0%
–17.593%
v17.607%
AddFEM
C79000–G8076–C900–03
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Dec.
Hex.
32764
7FFC
32512
7F00
32508
7EFC
27652
6C04
27648
6C00
4
4
0
0
–4
FFFC
–4864
ED00
–4868
ECFC
–32768
8000
Dec.
Hex.
32764
7FFC
32512
7F00
32508
7EFC
27652
6C04
27648
6C00
4
4
0
0
–4
FFFC
–4864
ED00
–4868
ECFC
Measuring range
0...20 mA
0...10 V
23.696 mA
11.848 V
23.511 mA
11.756 V
20 mA
10 V
0.002893 mA
0.0014468 V
0 mA
0 V
–3.511 mA
–1.756 V
Meeasuring range
4...20 mA
Remark
22.96 mA
Overflow
22.81 mA
Overrange
20 mA
Nominal range
0.002315 mA
4 mA
3.998 mA
Underrange
1.185 mA
Wire break
Technical Data
Remark
Overflow
Overrange
Nominal range
Underrange
Underflow
4-25

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents