Configuration
3.20 Configuring data points
The table lists the supported data point types of the modules with the classifications of the
protocol and the compatible S7 data types of the CPU.
Note
Effect of the change of arrays for data points
If an array is modified later, the data point must be recreated.
Data point types
Table 3- 4
Data point types, DNP3 object groups, variants and compatible S7 data types
Format (memory
Data point type
requirements)
Bit
Binary Input
Binary Input Event
Binary Output
Binary Output Event
Binary Command
Integer (16 bits)
Counter
Frozen Counter
Counter Event
Frozen Counter
Event
Analog Input
Analog Input Event
Analog Output Sta-
tus
Analog Output
Analog Output
Event
Integer (32 bits)
Counter
Frozen Counter
Counter Event
Frozen Counter
Event
Analog Input
Analog Input Event
Analog Output Sta-
tus
Analog Output
Analog Output
Event
110
DNP3 object
group
1)
11 [1, 2]
1)
21 [2, 6]
2)
22 [2, 6]
23 [2, 6]
3)
4)
42 [2, 4]
4)
21 [1, 5]
2)
22 [1, 5]
23 [1, 5]
3)
40 [1, 3]
4)
4)
Direction
[variation]
1 [1, 2]
in
2 [1, 2]
in
10 [2]
out
out
12 [1]
out
20 [2]
in
in
in
in
30 [2]
in
32 [2]
in
40 [2]
out
41 [2]
out
out
20 [1]
in
in
in
in
30 [1]
in
32 [1]
in
out
41 [1]
out
42 [1]
out
Configuration Manual, 11/2018, C79000-G8976-C508-01
S7 data types
CP
TIM
Bool
Bool
Bool
Bool
Bool
Bool
Bool
Bool
Bool
Byte
UInt, Word Word
UInt, Word Word
UInt, Word Word
UInt, Word Word
Int
Int
Int
Int
Int
Int
Int
Int
Int
Int
DWord
DWord
DWord
DWord
DWord
DWord
DWord
DWord
DInt
-
DInt
-
DInt
DWord
DInt
DWord
DInt
DWord
Operand area
I, Q, M, DB
I, Q, M, DB
Q, M, DB
Q, M, DB
Q, M, DB
I, Q, M, DB
I, Q, M, DB
I, Q, M, DB
I, Q, M, DB
I, Q, M, DB
I, Q, M, DB
Q, M, DB
Q, M, DB
Q, M, DB
I, Q, M, DB
I, Q, M, DB
I, Q, M, DB
I, Q, M, DB
Q, M, DB
Q, M, DB
Q, M, DB
Q, M, DB
Q, M, DB