Telecontrol via SINEMA RC

For information on possible applications of communication via SINEMA Remote Connect,
see section Connection to SINEMA RC (Page 161).
Requirements
Configure the SINEMA Remote Connect - Server before configuring the CP (not in STEP 7).
The CP and the communication partner of the CP must be configured in the SINEMA RC
Server.
Supported telecontrol protocols
The following protocols support communication via SINEMA Remote Connect:
● TeleControl Basic
● DNP3
● IEC 60870-5-104
Configuration of the telecontrol communication via SINEMA Remote Connect
Follow the steps below when configuring the CP for use of telecontrol communication via
SINEMA RC:
1. In the "Communication types" parameter group activate telecontrol communication and
select the protocol.
The option for communication via SINEMA RC is not yet visible.
2. Change to the "Security" parameter group and enable the security functions.
(In the "Communication types" parameter group the SINEMA RC option appears disabled
and grayed out)
3. Open the "Security > VPN" parameter group and enable VPN.
4. For the parameter "VPN connection type" select the option "Automatic OpenVPN
configuration via SINEMA Remote Connect Server" if this is not preset.
(In the "Communication types" parameter group the SINEMA RC option becomes
usable.)
5. Change to the "Communication types" parameter group and enable the option
"Telecontrol communication via SINEMA Remote Connect".
6. Create the remaining configuration of the SINEMA RC connection of the CP under
"Security > VPN".
For information on the configuration, see section Security > VPN > SINEMA Remote
Connect (Page 164).
Configuration - DNP3
Configuration Manual, 11/2018, C79000-G8976-C508-01
SINEMA Remote Connect (CP)
B.3 Telecontrol via SINEMA RC
163