Configuration
3.20 Configuring data points
No specific parameters are available for the output option LATCH_ON/OFF. The station
module evaluates the control codes of the master station according to the table above.
PULSE_ON parameters
Master
Name:
Range of val-
ues:
Default:
Explanation:
Name:
Range of val-
ues:
Explanation:
Name:
Range of val-
ues:
Default:
Explanation:
Name:
Range of val-
ues:
Default:
Explanation:
Station
Name:
Range of val-
ues:
Default:
128
Number of pulses
1 ... 255
1
Number of pulses that the data point of the master sends to the correspond-
ing data point of the station.
Puls-Steuerung
• NUL
• CLOSE
• TRIP
Trip-Close Code for Control Code "PULSE_ON". The data point sends the
configured code to the corresponding data point of the station. See above for
the meaning.
Pulse ON duration
0 ... 4294967295
10
Duration (milliseconds) for "On-time". The data point sends the configured
time to the corresponding data point of the station.
Pulse OFF duration
0 ... 4294967295
0
Duration (milliseconds) for "Off-time". The data point sends the configured
time to the corresponding data point of the station.
Max. number of pulses
0 ... 255
1
Configuration Manual, 11/2018, C79000-G8976-C508-01
Configuration - DNP3