Configuration
3.3 Basic settings / Options
You set the general behavior via the following parameters:
● Activate retentive saving
Activates the retentive saving of events on the SD card in the event of connection
disruptions.
● Number of events before saving
Saving events on the SD card starts when the number of events in the send buffer
configured here is reached after a connection failure.
● Interruption time before saving
Saving events on the SD card starts when the time of the connection interruption
configured here is reached.
For the maximum number of savable events, see section Performance data and
configuration limits (Page 16).
IP routing
These parameters are available with the TIM 1531 IRC.
Note
The function is not intended for large data volumes.
Restrict routing via the TIM to approx. 1 Mbit/s so that productive operation of the TIM is not
impaired.
IP routing
● Allow IP routing
Enables IP routing via the interfaces of the module.
● Routing method
Defines the paths for IP routing:
– Local: IP routing only between the Ethernet interfaces of the module
– Via subnets: IP routing via a maximum of 10 configurable routers that can be
Router addresses
● Ethernet interface
Ethernet interface of the module via which IP routing is to be configured. The IP
addresses of the interfaces used for IP routing need to be permanently configured.
An interface can be selected several times for different routes.
34
accessed via the module's interfaces.
Configuration Manual, 11/2018, C79000-G8976-C508-01
Configuration - DNP3