Configuration

3.21 Configuring messages

3.20.11

Partner stations

Activating the partners of the data point
All partners with which a telecontrol connection has been configured are shown in the table.
Enable the partner or partners with which the selected data point is to exchange data using
the check box:
3.21
Configuring messages
3.21.1

Messages

Calling the editor
You configure the messages in STEP 7 in the data point and message configuration. You
can find this using the project tree:
Project > directory of the relevant station > Local modules > Module
For the view in STEP 7, refer to the section Data point configuration (Page 103).
Alternatively, you can get to the editor via the shortcut menu when the module is selected in
the network view.
E-mails
If important events occur, the module can send e-mails. The recipient can be a PC with an
Internet connection or an S7Station.
130
• Select and operate
Procedure:
– The command is triggered in the master module
The "select" frame is sent from the master station to the communication
module of the station.
– The station acknowledges receipt.
– The master data point sends the execution frame after receiving the
acknowledgment from the station.
– The station only forwards the command to the CPU when it receives
the "Operate" frame from the master within the configured "Max. time
between Select and Operate".
The station must not receive any other data frame between Select and
Operate.
Note: "Max. time between Select and Operate" is configured in the
transmission settings of the respective interface.