Siemens SIMATIC TeleControl DNP3 Configuration Manual page 127

Hide thumbs Also See for SIMATIC TeleControl DNP3:
Table of Contents

Advertisement

Table 3- 6
Control
Code
0x01
0x03
0x04
0x41
0x81
Note
Mirroring
If you want the station data point to mirror the current value back to the master, enable the
"Value monitoring" option in the "General" tab of the data point.
Selection of the control code
Name:
Range of val-
ues:
Explanation:
Select the desired output option.
Configuration - DNP3
Configuration Manual, 11/2018, C79000-G8976-C508-01
Decoding of the control code by the command data point of the station
Received control code
Trip-
Operation
Close
Type Field
Code
NUL
PULSE_ON
NUL
LATCH_ON
NUL
LATCH_OFF •
CLOSE
PULSE_ON
TRIP
PULSE_ON
Control Code
• PULSE_ON
• LATCH_ON/OFF
Output option of the command output. See above for the meaning.
Reaction of the station data point
Option enabled:
PULSE_ON
The output is set to 1 for the
duration of "On-time".
CP
The command is rejected.
TIM 1531 IRC
The output is set to 1 for the
duration of "On-time".
CP
The command is rejected.
TIM 1531 IRC
The output is set to 1 for the
duration of "On-time".
CP
The command is rejected.
TIM 1531 IRC
The output is set to 1 for the
duration of "On-time".
CP
The command is rejected.
TIM 1531 IRC
The output is set to 1 for the
duration of "On-time".
Configuration
3.20 Configuring data points
Option enabled:
LATCH_ON / OFF
The command is rejected.
The output is set to 1.
The output is set to 0.
CP
The command is rejected.
TIM 1531 IRC
The output is set to 1.
CP
The command is rejected.
TIM 1531 IRC
The output is set to 0.
127