Diagnostics; Events; C.7 Diagnostics - Siemens SIMATIC TeleControl DNP3 Configuration Manual

Hide thumbs Also See for SIMATIC TeleControl DNP3:
Table of Contents

Advertisement

WBM of the TIM 1531 IRC

C.7 Diagnostics

C.7

Diagnostics

C.7.1

Events

Diagnostics messages
Table
The table lists the last diagnostics events to occur on the TIM with the following information:
● Number
Consecutive number
● Time
Time of the diagnostics event
● Date
Date of the diagnostics event
● Event type
The diagnostics messages are classified as follows:
– INFO
– WARNING
– ERROR
– FATAL
● Event
Plain text of the diagnostics event
Copy of the diagnostics buffer
Using the button, you save the content of the diagnostics buffer on the PC.
The diagnostics buffer
The diagnostics buffer receives diagnostics messages for internal events and errors. It can
hold a maximum of 200 entries. When the maximum number is exceeded, the oldest entries
are overwritten.
The entries in the diagnostics buffer contain a consecutive number, a classification, a time
stamp and the message text.
176
Information about a special event
Warning of a possibly unwanted event
Internal error. The TIM starts up.
Serious error that impairs or interrupts the operation of the TIM.
Configuration Manual, 11/2018, C79000-G8976-C508-01